Functional characteristics of temperature transmitter
Linearized output 4-20mA standard current signal
Adopting epoxy resin casting process, shockproof and moisture-proof
Thermocouple transmitter cold end automatic compensation
The temperature module adopts an epoxy resin casting process inside, which is suitable for use in various harsh and dangerous places.
The use of thermocouple temperature variation eliminates the need for compensating wires.
Main technical specifications of temperature transmitters
Output: 4-20mA, maximum 28mA
Input range: Thermal resistance: Pt100, -200-500 ℃; Cu50, -50-150 ℃
Thermocouple: K-type, 300-1200 ℃; E-type, 200-800 ℃;
S-type, 600-1600 ℃
Fusing detection: upper limit (standard)
Measurement accuracy: Thermal resistance: ± 0.25% FS
Thermocouple/mV: ± 0.3% FS~± 0.5% FS
Temperature drift: ± 0.02% FS/℃
Cold end compensation: 0-50 ℃ ± 10%
Adjustment method: potentiometer