The intelligent inspection instrument is suitable for detecting and alarming process quantities from 5 to 80 points. Can input sensor and transmitter signals such as thermal resistance, thermocouple, DC current, DC voltage, etc.
Basic error less than 0.2% F · S, display range -1999~9999
Set input signal type, range, and alarm value for each channel
Set digital filtering time constants for each channel to effectively improve anti-interference ability
Set zero and full scale corrections for each channel, effectively reducing sensor errors and improving system measurement accuracy
Can close unused channels at will
Level 2 parameters. The second level parameters are password controlled to prevent accidental operations. Equipped with parameter copying function, greatly reducing the workload of parameter settings
Extremely practical alarm function, can be connected to multi-point control units to achieve alarm output for each channel
Manual, timed, and alarm start printing
Quick and effective communication interface, greatly reducing communication time
2、 Selection table for intelligent inspection equipment:
Note: Matching can achieve alarm output for each channel. Each unit * * has an additional 16 control outputs, and each meter * * can use up to 2 to achieve 32 point control.
The multi-point control unit is used in conjunction with the inspection instrument, and through the matching multi-point control unit, the alarm status of each channel can be directly output or combined output.
To achieve the purpose of alarm or control for each channel.
Note: 1. The standard configuration includes 4-point control
2. All 16 control points can be selected as relay outputs or solid-state outputs, or different control outputs can be corresponding to different points, but they should be specified when ordering.
3、 Technical specifications of intelligent inspection instrument:
Input
Number of channels: 5-80 channels
Thermal resistance: Pt100, Cu100 , Cu50 , BA1 , BA2 , G53
Full range measurement, display resolution of 0.1 ℃, with wire breakage recognition function
Thermocouples: K, S, R, B, N, E, J, T, etc
Full range measurement (including negative temperature), display resolution of 1 ℃ or 0.1 ℃, selected through parameters. With wire breakage recognition function
DC current: 4mA~20mA, 0mA~10mA, 0mA~20mA, display range -1999-9999, with arbitrary range and decimal point position settings
DC voltage: 1V~5V, 0V~5V, display range -1999-9999, freely set range and decimal point position
Thermal resistance input wire resistance: within 20 Ω
Thermocouple input wire resistance: within 100 Ω
Accuracy
Using a 16 bit A/D converter
Measurement accuracy: ± 0.2% F · S
Display resolution: 1/10000
Thermocouple cold end compensation accuracy: ± 0.2 ℃, range 0 ℃~60 ℃